| WELCOME
TO THE RICKARD-AIR VARIABLE GEOMETRY VAV SYSTEMS |
VAV
SYSTEM DESIGN
Generally
the design considerations governing constant volume air conditioning
systems can be applied to the design of air handling and distribution
equipment for variable volume systems. Whilst the subjects
of heat loads and air quantity or temperature calculations
are fully dealt with in such publications as the ASHRAE guide,
the following general procedure is recommended:
-
Cooling and heating load calculations are made for every
module or zone in the building so that individual maxima
and simultaneous maximum cooling/ heating requirements and
air quantities can be established.
-
The design temperature of supply air at the terminal (allowing
for all normally calculated extraneous gains such as fan
heat and duct wall heat pick-up) is arrived at by conventional
psychometric calculations.
-
Individual maximum module or zone air volumes are calculated
using the maximum room sensible heat gain figure and the
temperature difference between supply air temperature at
the terminal and design space temperature. These air volumes
are then used to select air diffusers.
-
Maximum simultaneous cooling and air supply requirements
are then computed in order to establish the capacity of
air handling units and central cooling equipment. Care must
be taken in design that ducting is adequately sized to convey
the correct amount of air to every module or zone under
all conditions.
OTHER
DESIGN CONSIDERATIONS TO BE NOTED ARE:
Control of duct Pressure
The
control of supply air duct static pressure within the design
limits of the terminal units is an essential requirement of
variable volume systems and such control is easily achieved
by any or a combination of the following methods, depending
on the size and configuration of the air distribution system:
- Control
of supply air duct fan output by means of a static pressure
regulator operating in conjunction with its capacity modulation
device. In smaller systems this device need be no more than
fan motor speed control although acceptable performance
will probably be achieved with a face and by-pass damper
configuration.
- Dividing
the air distribution systems into the most conveniently
selected low pressure supply duct zones, supplied from low/medium
pressure main ducts or risers, by the fitting of branch
duct dampers operating in conjunction with branch supply
duct static pressure regulators.
Duct Static Pressure Variations
Design and manufacturing discrepancies in supply duct systems
are largely compensated for by terminal volume adjustment
in response to thermostat action. Tolerances of - 10% to +20%
in duct static pressure will not materially effect correct
functioning of variable volume terminal units. Under all terminal
output conditions duct pressure variations will be compensated
for by temperature controllers which react to an incorrect
supply of air by terminal volume regulation. At minimum flow,
variations in duct static pressure are normally slight as
duct pressure losses at low air flow are almost non-existent.
Recommended Branch Duct Pressure
The
determination of design branch duct pressure should be governed
by the noise levels to be satisfied, the area the conditioned
air should serve, or throw and the duct pressure needed to
deliver the air flow required by thermal load calculations.
All these details are provided in the relevant sections of
the manual.
Recommended Main Duct or Riser Pressure
For
economical fan operation, this pressure should be just high
enough to accommodate main duct or riser pressure losses and
design tolerances. With careful riser duct design it should
not be necessary to require riser or main duct pressure to
be more than 0.4 in.w.g. above branch duct pressure.
Positioning
of Static Pressure Sensors
In all cases static pressure sensors for branch ducts should
be fitted in the branch ducts themselves and not in the feeder
ducts to individual terminals nor in the terminal units themselves.
Generally it is recommended that static pressure sensors in
branch ducts be fitted half-way between the duct pressure
control damper or supply fan and the end of the relevant duct
so that the most representative pressure is sensed.
Branch
Duct Velocities
In the case of branch ducts serving terminal units it is recommended
that conventional criteria be used in the determination of
branch duct velocities, and it is assumed that, depending
on noise level requirements these will be in the range of
700 - 1200 ft/min. In some cases slightly higher branch duct
velocities are allowed because of the inherent noise attenuation
properties of the terminal units with associated flexible
duct connections. Generally a maximum of 1500 ft/min is recommended.
In the case of smaller air handling units of the fan/coil
type incorporating light duty centrifugal fans, volume modulation
is most easily achieved by fitting supply duct restrictors
and bypass dampers. This system is also used when packaged
air handling equipment is selected.
Cooling plants of the direct expansion type - generally cheaper
to install and operate than chilled water generating plants
- can be used for virtually every application. Limitations
of this type of plant are imposed only by capacity. In the
case of smaller plants where cooling is controlled in only
one or two steps, the temperature sensor for cooling control
should be placed in the "warmest" room. This avoids
short-cycling of the compressors, which would result if the
off-coil temperature were to be measured and controlled. Generally
individual reciprocating compressor cooling stations are limited
to a capacity of 45 tons refrigeration, above which the economics
of centrifugal or screw type chilled water generators begin
to influence the choice.
High Velocity System
Building
space limitations may dictate the use of high velocity systems,
obviously at an operating cost premium due to the resultant
higher fan duties. At the point of change from high velocity,
pressure reducing dampers are fitted. Each damper unit requires
a sound attenuator to reduce high velocity duct and damper
noise generated through pressure reduction.
UNITED
STATES OFFICE
Rickard Air Diffusion, 1401 N. Plano Road, Richardson, TX. 75081
TEL: (972) 744 9090, FAX: (972) 238 0641
HEAD OFFICE RICKARD AIR DIFFUSION (PTY) LTD,
P.O. BOX 103 OTTERY 7808,
Tel : ++27 (021) 704 1533 Fax: ++27 (021) 704 1004
|